SteelPro HD180 Interior Intumescent Steel Fire Protection

Quick Specs

SteelPro HD180 Interior Intumescent Fire Protection Coating for Steel Structures is a fire protection coating. Suitable for fire protection of steel columns, beams, supports, floors and profiled steel sheets in steel structures, such as civil steel buildings, commercial buildings, gymnasiums, airports, stations, large shopping malls and industrial plants. T&H Fire Shield acrylic SteelPro HD180 is a water-borne fire protection coating composed of water-borne resin, quality chemical flame retardants and additives, tested and certified to the steel structure fire protection coating standard GB 14907-2018, a product with high fire protection performance, whose main characteristics are as follows. Parameters on this page: volume solids 72 ± 3%; dry film thickness 700/1500/2500 µm; theoretical spreading rate 0.29 m²/L.

Parameter source: T&H original technical data sheet (TDS) "SteelPro HD180 Interior Intumescent Fire Protection Coating for Steel Structures"; values such as spreading rate are converted from TDS parameters and are for selection reference only.
The above content is compiled from the manufacturer's datasheet and this site's parameter tables. For selection, coating systems and lead times, pleaseContact Usfor confirmation.

This page carries the full TDS for this product, translated from the manufacturer's original document. No file download is needed; for an original-language copy, send an enquiry.

Volume Solids72 ± 3%
Dry Film Thickness700/1500/2500 µm
Theoretical Spreading Rate0.29 m2/L
VOC20g/L
Density / Specific Gravity1.4 ± 0.1 kg/L
Number of ComponentsOne-component
Flash Point>100°C
ThinnerWater
Wet Film Thickness975/2085/3475 µm

Browse Similar Models by CategoryThis model belongs to: Fire Protection

FAQ

How many components does SteelPro HD180 contain?
SteelPro HD180 is a one-component product. Stir thoroughly before use; no on-site mixing is required.
What is the typical dry film thickness of SteelPro HD180?
Typical dry film thickness of SteelPro HD180: 700/1500/2500 µm; final value depends on the coating system and design requirements.
What is the theoretical spreading rate of SteelPro HD180?
Theoretical spreading rate of SteelPro HD180: 0.29 m²/L; actual consumption varies with substrate roughness, application loss and colour hiding power.
What is the volume solids of SteelPro HD180?
Volume solids of SteelPro HD180: 72 ± 3%.
What is the VOC of SteelPro HD180?
VOC of SteelPro HD180: 20 g/L.
Which thinner is recommended for SteelPro HD180?
Recommended thinner for SteelPro HD180: water.
What is the flash point of SteelPro HD180?
The flash point of SteelPro HD180 is >100 °C; storage, transport and application shall comply with the product Safety Data Sheet.
Which standards apply to SteelPro HD180?
As recorded in the technical data on this page: tested and certified to the fireproof coating standard for steel structures GB14907-2018; a product with excellent fire performance, whose main characteristics are as follows; ISO8501 (see the application instructions on this page). Specific applicability is subject to the manufacturer's technical data sheet and the coating system.
Where can SteelPro HD180 be purchased?
RichTech Industrial Technology (Shanghai) Co., Ltd. distributes industrial and marine coatings, representing brands including JOTUN, HEMPEL, International, PPG and KANSAI, and provides product selection, coating systems and quantity calculations. Company address: Changhui Building, 799 Yinxiang Road, Jiading District, Shanghai.
Interior intumescent fire protection for structural steelSteelProHD180

Product introduction and characteristics

T&H Fire Shield acrylic SteelPro HD180 is a water-borne fire protection coating composed of water-borne resin, quality chemical flame retardants and additives, tested and certified to the steel structure fire protection coating standard GB 14907-2018, a product with high fire protection performance, whose main characteristics are as follows:

Product use

Suitable for fire protection of steel columns, beams, supports, floors and profiled steel sheets in steel structures, such as civil steel buildings, commercial buildings, gymnasiums, airports, stations, large shopping malls and industrial plants.

Basic physical and chemical data

Colour: white/grey-white

Gloss: not applicable

Density: 1.4 ± 0.1 kg/L

Volume solids: 72 ± 3%

VOC: 20 g/L

Flash Point >100 °C

Mixing ratio: single component

Pot life (25 °C): not applicable

Fire resistance and certification

Areas of useFire resistance classification codeGB 14907-2018 corresponding report product model

Compliance

InteriorFp1.50GT-NSP-Fp1.50-HD-180
InteriorFp2.00GT-NSP-Fp2.00-HD-180
InteriorFp2.50
OutdoorFp3.00GT-WSP-Fp2.00-HD-180
OutdoorFt1.00GT-WSP-Ft1.00-HD-180
OutdoorFt1.50GT-WSP-Ft1.50-HD-180
OutdoorFt2.00GT-WSP-Ft2.00-HD-180

Approval/compliance: CCCF certified by the Fire Product Compliance Assessment Centre of the Ministry of Emergency Management, in accordance with national standard

Product tested and assessed per GB 14907-2018 steel structure fire protection coating requirements

Application parameters

Typical dry film thickness: 700 µm. Recommended dry film thickness: 300–700 µm depending on system requirements. Induction time (25 °C): none. Application methods:

ThinnerAirless spray — waterAir spray /Roller or brush — water
Thinner quantity (by volume)0-5%/0-5%
Recommended nozzle size0.43~0.58mm/
Recommended spray pressure15~20MPa/
Application suitabilityRecommendedN/AApplicable

Theoretical spreading rate:

Dry film thickness (µm)70015002500
Wet film thickness (µm)97520853475
Theoretical spreading rate (m²/L)1.030.480.29

Surface Preparation

Before application, blast-clean the substrate to Sa 2.5 (ISO 8501-1) and apply a suitable primer. Remove grease with a suitable cleaning agent and wash off salts and other contaminants with high-pressure clean water. Repair any damage to the anti-rust primer before applying the fire protection coating. On steel already coated with anti-rust primer, check the compatibility between the primer and the fire protection coating.

Precautions

1) During application, the steel surface temperature must be 10–45 °C. The surface temperature must be at least 3 °C above the dew point and the maximum relative humidity must not exceed 85% during application. During application, ensure ventilation and exhaust, keep away from ignition sources, and wear protective equipment such as masks and gloves; maintain adequate ventilation during curing. 2) This product can be thinned as required by adding tap water; mix thoroughly and strain through a 120-mesh copper screen before use. Seal unused paint that will not be used for a long time, otherwise skinning may occur. If skinning occurs, strain out the skin before use. 3) To achieve full performance, reaching the specified dry film thickness is essential. The dry film thickness also depends on the shape and size of the steel. The applicator must ensure all areas of the steel reach the specified dry film range. Whether by airless spray or brush/roller, the fire protection coating must be applied in multiple coats to reach the specified dry film thickness. For the first coat, thin the coating and control the thickness at 0.30–0.50 mm; apply the next coat after drying for more than 6 hours (20 °C, 65% RH), controlling at 0.40–0.70 mm. Before applying the topcoat, the fire protection coating must dry for at least 48 hours. 4) Apply only over primers approved by the company; consult the company's technical representative regarding approved primers. This product is supplied in white only. Depending on the purpose of the system, a compatible approved topcoat may be required; consult the company's technical representative on which topcoat to use. 5) This product has a high viscosity and may show false-body (thixotropic) thickening in storage. Stir briefly before application to mix evenly and break the false body, ensuring good flow during application; excessive stirring may cause solvent loss. The product is thermoplastic and ductile; above 40 °C the film may show indentation under mechanical action, and the mechanical strength recovers when the temperature drops. 6) During work breaks, do not leave paint in the hose, spray gun or spray equipment. Flush all equipment thoroughly with thinner. 7) Clean all equipment with thinner immediately after use. Flushing spray equipment regularly during work is good practice. Cleaning frequency depends on spray volume, temperature and spraying time including interruptions. 8) The fire protection coating must not be exposed to rain during application and curing; handle with care. Before and during use, avoid inhaling spray mist and minimise skin and eye exposure, and avoid contact with wet paint. Without a topcoat or temporary waterproof layer, the fire protection coating has only limited water resistance. Move the coated item outdoors for curing only after a topcoat or temporary waterproof layer is applied. 9) Dispose of leftover paint and empty cans in accordance with local regulations.

Packaging

20 kg/drum

Storage

Keep sealed in a ventilated, cool, dry place away from sources of ignition. Minimum 12 months.

Safety Precautions

1) For the paint and recommended thinners, refer to the safety data sheet and related material safety data. Although this is a water-borne coating, avoid inhaling spray mist and minimise skin and eye exposure, and avoid contact with wet paint. 2) All work related to the application and use of this product must comply with the relevant national health, safety and environmental standards and regulations. 3) Welding or flame cutting on metal coated with this product produces dust and fumes; use appropriate personal protective equipment and adequate local ventilation. 4) If in doubt about the suitability of this product, consult the company.

Scope of liability

The information in this datasheet is based on laboratory test results which the company believes to be accurate, and is provided for application guidance only. T&H provides advice and recommendations regarding its products, whether in technical documents, in response to specific enquiries or otherwise, based on information believed to be reliable. The products and information are intended for users with the necessary knowledge and industrial experience; the end customer is responsible for determining their suitability for the intended use. T&H cannot control the quality and condition of the substrate or the various factors affecting product use. Accordingly, T&H accepts no liability for any loss, injury or damage arising from the use of its products or from reliance on this datasheet (unless otherwise agreed in writing). The data in this datasheet may be revised as necessary based on practical experience and continuous product development. Publication date: June 2022.

Information is subject to the manufacturer's latest version; the manufacturer's latest TDS prevails.
The technical parameters on this page are taken from the product's original manufacturer technical datasheet, the copyright of which belongs to the manufacturer. If a rights holder considers the presentation inappropriate, contact us for verification and handling.

Purchase & Documents

Packaging specifications and batch lead times are subject to actual availability. PleaseContact Uscontact us for project-based calculation.

China production baseIndustrial & marine coatingsWorldwide delivery