← Back to T&H brand page
China-based coatings exporter — industrial & marine protective coatings from China's production bases

SteelPro FM119 Exterior Intumescent Steel Fire Protection

Quick Specs

SteelPro FM119 Exterior Intumescent Fireproof Coating for Steel Structures belongs to Fire Protection. T&H Fire Shield Acrylic SteelPro FM119 is a solvent-borne fireproof coating composed of acrylic resin, high-quality chemical flame retardants, additives and solvents, certified to GB14907-2018, the standard for fireproof coatings for steel structures. The product with excellent fire performance is suitable for fire protection of steel structures such as steel columns, steel beams, supports, floors and steel corrugated sheets in civil steel structures, commercial buildings, TV towers, stadiums, airports, stations, large shopping malls and industrial plants. Parameters on this page: volume solids 76 ± 3%, dry film thickness 500/750/1000 µm, theoretical spreading rate 0.76 m2/L.

Parameter source: T&H manufacturer's Technical Data Sheet (TDS) "SteelPro FM119 Exterior Intumescent Steel Fire Protection"; spreading rate and other values are converted from the TDS parameters and provided for product selection reference only.
The above content is compiled from the manufacturer's datasheet and this site's parameter tables. For selection, coating systems and lead times, pleaseContact Usfor confirmation.

This page carries the full TDS for this product, translated from the manufacturer's original document. No file download is needed; for an original-language copy, send an enquiry.

Volume Solids76 ± 3%
Dry Film Thickness500/750/1000 µm
Theoretical Spreading Rate0.76 m2/L
VOC330g/L
Density / Specific Gravity1.35 ± 0.1 kg/L
Number of ComponentsOne-component
Flash Point26°C
ThinnerXH9010
Wet Film Thickness658/987/1316 µm

Browse Similar Models by CategoryThis model belongs to: Fire Protection

FAQ

How many components does SteelPro FM119 have?
SteelPro FM119 is a one-component product; stir thoroughly after opening the can before application, no on-site mixing required.
What is the typical dry film thickness of SteelPro FM119?
The typical dry film thickness of SteelPro FM119 is 500/750/1000 µm, determined by the coating system and design requirements.
What is the theoretical spreading rate of SteelPro FM119?
The theoretical spreading rate of SteelPro FM119 is 0.76 m2/L; actual consumption is adjusted according to substrate roughness, application loss and colour hiding power.
What is the volume solids of SteelPro FM119?
The volume solids of SteelPro FM119 is 76 ± 3%.
What is the VOC of SteelPro FM119?
The VOC of SteelPro FM119 is 330g/L.
What thinner is used for SteelPro FM119?
Recommended thinner for SteelPro FM119: XH9010.
What is the flash point of SteelPro FM119?
The flash point of SteelPro FM119 is 26 °C; storage, transport and application shall follow the product safety data sheet.
Which standards are involved for SteelPro FM119?
As recorded in the technical data on this page: GB14907-2018 (see the application instructions on this page); all surfaces shall be assessed and prepared in accordance with ISO 8504:2000. Specific applicability is subject to the manufacturer's technical data sheet and the coating system.
Where can SteelPro FM119 be purchased?
RichTech Industrial Technology (Shanghai) Co., Ltd. distributes industrial and marine coatings, representing brands including JOTUN, HEMPEL, International, PPG and KANSAI, and provides product selection, coating systems and quantity calculations. Company address: Changhui Building, 799 Yinxiang Road, Jiading District, Shanghai.

Product Description

T&H Fire Shield Acrylic SteelPro FM119 is a solvent-borne fireproof coating composed of acrylic resin, high-quality chemical flame retardants, additives and solvents, certified to GB14907-2018, the standard for fireproof coatings for steel structures. The product with excellent fire performance is suitable for fire protection of steel structures such as steel columns, steel beams, supports, floors and steel corrugated sheets in civil steel structures, commercial buildings, TV towers, stadiums, airports, stations, large shopping malls and industrial plants.

Product Characteristics

the independent weather resistance of the fireproof coating can reach 12 months.

Basic physical and chemical data

Colour: White

Gloss: not applicable

Density: 1.35±0.1 kg/L

Volume Solids: 76±3%

VOC: 330g/L

Flash Point 26 °C

Mixing ratio: single component

Pot life (25 °C): not applicable

Fire resistance and certification

Areas of useFire resistance classification codeGB 14907-2018 corresponding report product model

Compliance

OutdoorFp1.00GT-WRP-Fp1.00-FM119
OutdoorFp1.50GT-WRP-Fp1.50-FM119
OutdoorFp2.00GT-WRP-Fp2.00-FM119
OutdoorFp2.50
OutdoorFt1.00GT-WRP-Ft1.00-FM119
OutdoorFt1.50GT-WRP-Ft1.50-FM119
OutdoorFt2.00GT-WRP-Ft2.00-FM119

Approval/compliance: CCCF certified by the Fire Product Compliance Assessment Centre of the Ministry of Emergency Management, in accordance with national standard

Product tested and assessed per GB 14907-2018 steel structure fire protection coating requirements

Application parameters

Typical DFT: 750µm Recommended DFT: According to different fire resistance requirements and fire protection standards of the project, XINHE New Materials Co., Ltd. will recommend the corresponding spray thickness. ※ For details, please consult XINHE New Materials Co., Ltd.

Application Methods: Airless Spray, Air Spray, Roller or Brush

ThinnerXH9010/XH9010
Thinner quantity (by volume)0-15%/5-15%
Recommended nozzle size0.43~0.58mm/
Recommended spray pressure15~20MPa/
Application suitabilityRecommendedN/AApplicable

Theoretical spreading rate:

Dry film thickness (µm)5007501000
Wet film thickness (µm)6589871316
Theoretical spreading rate (m²/L)1.521.010.76

Application Data (typical DFT 750µm):

TemperatureSurface DryDry to handlePot LifeSelf-overcoating interval
MinimumMaximum*
5°C60min36h/32h/
15°C40min15h/13h/
25°C25min7h/5.5h/
40°C<10min4h/4h/

The drying times listed in the above table are measured at a typical thickness of 750 µm under controlled temperature and relative humidity of 50%~75% with good ventilation.

*The maximum overcoating interval depends on the exposure environment and use of the coating, and normally shall not exceed 12 months.

Surface Preparation

8504:2000. If grease is present, clean with solvent according to SSPC-SP1.

cleaner to thoroughly remove grease, etc., and high-pressure clean water to remove salts and other contaminants. Steel must be coated with a primer approved by the company. Where conditions are limited, mechanical grinding to St3 is also acceptable; see the relevant requirements in the application guide.

guide.

Precautions

1. The steel surface temperature during application of this product shall be 5~50 °C. The surface temperature must be at least 3 °C above the dew point, and the maximum relative humidity during application must not exceed 85%; ensure ventilation and exhaust during application, keep away from ignition sources, wear masks, gloves and other protective equipment, and maintain adequate ventilation during curing. 2. This product may be diluted as required, but excessive thinner will cause a risk of sagging; adjust the thinner amount according to temperature changes, mix thoroughly, and filter through a 120-mesh copper wire screen before use. Unused paint must be sealed when not used for a long period, otherwise skinning may occur. If skinning occurs, filter out the skin from the paint before use. 3. To ensure full performance of this product, it is important to achieve the specified dry film thickness. The dry film thickness of this product also depends on the shape and dimensions of the steel. Applicators must ensure that all areas of the steel reach the specified dry film range. Whether by airless spray or brush/roller, the fireproof coating must be applied in multiple coats to achieve the specified dry film thickness. For the first coat, dilute the fireproof coating to a film thickness of 0.25~0.35mm, and allow to dry for more than 6 h (20 °C, relative humidity 65%) before applying the next coat. It is recommended that the typical dry film thickness per spray coat is 750 µm (undiluted), and the maximum dry film thickness per roller coat is recommended to be 400 µm (undiluted). Applying higher film thickness may easily cause sagging and unacceptable solvent retention. 4. According to regulations, apply only over a primer approved by the company; please consult the company's technical representative regarding approved primers. This product is available only in white; depending on the purpose of the coating system, a coat of this product may be required

Compatible and approved topcoats; consult the company's technical representative regarding the selection of a topcoat for specific conditions. 5. This product has high viscosity and exhibits false body during storage. Stir briefly before application to mix uniformly and break the false body, ensuring good flow during application; excessive stirring may cause solvent evaporation. This product is thermoplastic and ductile; at temperatures above 40 °C, the film may show marks under mechanical action, and mechanical strength recovers when the temperature decreases. 6. When work is suspended, do not leave paint in the paint line, spray gun or spray equipment. Flush all equipment thoroughly with thinner. 7. All equipment shall be cleaned with thinner immediately after use. Periodic flushing of spray equipment during the daily work process is good practice. Cleaning frequency depends on spray volume, temperature, spray time, including interruption time and other factors. 8. Fire-retardant coatings shall not be exposed to rain during application and curing; handle with care. Before and during use, inhalation of paint mist must be avoided, skin and eye exposure shall be minimized, and contact with wet paint shall be avoided. Without a topcoat or intermediate waterproof layer, the fire-retardant coating has only limited water resistance. The fire-retardant coating may be moved outdoors for curing only after a topcoat or temporary waterproof layer has been applied. 9. Residual paint and empty containers shall be disposed of in accordance with applicable regional regulations.

Packaging

20 kg/drum

Storage

Keep sealed in a ventilated, cool, dry place away from sources of ignition. Minimum 12 months.

Safety Precautions

1. For the paint and recommended thinner, refer to the safety data sheet and the safety data of the relevant materials. Although this is a water-borne paint, inhalation of paint mist must still be avoided, skin and eye exposure shall be minimized, and contact with wet paint shall be avoided. 2. All work related to the application and use of this product must be carried out in accordance with the relevant national health, safety and environmental standards and regulations. 3. Welding or flame cutting on metal coated with this product generates dust and fumes; suitable personal protective equipment and adequate local ventilation are therefore required. 4. If there is any doubt about the suitability of this product, consult the company.

Scope of liability

The information provided in this product data sheet is based on laboratory test results we consider accurate and is intended for application guidance only. All opinions and recommendations of XINHE regarding the use of XINHE products, whether in technical documents, specific consultations or other forms, are based on information we consider most reliable. Our products and the information provided are intended for users with the requisite knowledge and industrial experience, and it is ultimately the end customers who shall determine whether these products are suitable for their use. XINHE cannot control the quality and condition of the substrate, nor the various factors affecting product use. Accordingly, XINHE assumes no liability for any loss, injury or damage arising from the use of its products or from reference to this product data sheet (unless otherwise agreed in writing). Data in the product data sheet will be revised as necessary based on practical experience and the need for continuous product development.

Information is subject to the manufacturer's latest version; the manufacturer's latest TDS prevails.
The technical parameters on this page are taken from the product's original manufacturer technical datasheet, the copyright of which belongs to the manufacturer. If a rights holder considers the presentation inappropriate, contact us for verification and handling.

Purchase & Documents

Packaging specifications and batch lead times are subject to actual availability. PleaseContact Uscontact us for project-based calculation.

China production baseIndustrial & marine coatingsWorldwide delivery