SteelMaster 900WF Interior Intumescent Steel Fire Protection

Quick Specs

SteelMaster 900WF Intumescent Fire Protection Coating for Interior Steel Structures is a fire protection coating. Designed for steel structures as an intumescent fire protection system, it is widely suited to I-beams, columns and hollow structural sections. Independently certified for fire protection of structural steel exposed to cellulosic fires. Parameters on this page: volume solids 73 ± 4%, dry film thickness 220–730 µm, number of components one-component. Comparable products of the same brand: Jotachar 1709 XT epoxy intumescent coating, Jotachar 1709 exterior intumescent fire protection coating for steel structures, Jotachar JF750 XT epoxy intumescent coating.

Parameter source: JOTUN manufacturer's Technical Data Sheet (TDS) "SteelMaster 900WF Intumescent Fire Protection Coating for Interior Steel Structures"; values such as spreading rate are converted from TDS parameters and are for product selection reference only.
The above content is compiled from the manufacturer's datasheet and this site's parameter tables. For selection, coating systems and lead times, pleaseContact Usfor confirmation.

This page carries the full TDS for this product, translated from the manufacturer's original document. No file download is needed; for an original-language copy, send an enquiry.

Volume Solids73 ± 4%
Dry Film Thickness220–730 µm
Theoretical Spreading Rate—
VOC22 g/L (US)
Density / Specific Gravity1.4 kg/L
Number of ComponentsOne-component
Flash Point101 °C
ThinnerFresh water
Wet Film Thickness300–1000 µm

Browse Similar Models by CategoryThis model belongs to: Fire Protection

FAQ

How many components does SteelMaster 900WF contain?
SteelMaster 900WF is a one-component product. Stir thoroughly in the can before application; no on-site mixing is required.
What dry film thickness is typically applied for SteelMaster 900WF?
SteelMaster 900WF is normally applied at a dry film thickness of 220–730 µm, depending on the coating system and design requirements.
What is the volume solids of SteelMaster 900WF?
The volume solids of SteelMaster 900WF is 73 ± 4%.
What is the VOC of SteelMaster 900WF?
The VOC of SteelMaster 900WF is 22 g/L (US).
What thinner is used for SteelMaster 900WF?
Recommended thinner for SteelMaster 900WF: fresh water.
What is the flash point of SteelMaster 900WF?
The flash point of SteelMaster 900WF is 101°C; storage, transport and application shall follow the product Safety Data Sheet.
How long does SteelMaster 900WF take to dry?
Drying time of SteelMaster 900WF under standard conditions: touch dry 4 h; actual results are affected by temperature, film thickness and ventilation.
Which standards apply to SteelMaster 900WF?
As recorded in the technical data on this page: EN13381 (see the application instructions on this page); EN 13501 (see the application instructions on this page). Specific applicability is subject to the manufacturer's technical data sheet and the coating system.
Where can SteelMaster 900WF be purchased?
RichTech Industrial Technology (Shanghai) Co., Ltd. distributes industrial and marine coatings, representing brands including JOTUN, HEMPEL, International, PPG and KANSAI, and provides product selection, coating systems and quantity calculations. Company address: Changhui Building, 799 Yinxiang Road, Jiading District, Shanghai.

SteelMaster 900WF

Product description

This is a single-component, thin-film intumescent water-borne acrylic coating. Independently certified for fire protection of structural steel exposed to cellulosic fires. In atmospheric environments, it may be used as an intermediate coat or topcoat. Suitable for carbon steel substrates coated with an approved primer.

Typical Use

Designed as an intumescent fire protection system for steel structures, widely applicable to various I-beams, columns and hollow sections. Suitable for steel structures exposed to internal environments.

Contact your local JOTUN representative for the detailed application procedure document.

Others

Approvals and Certificates

BS 476 Part 20/21: Certifire CF 6140 (fire resistance up to 150 min)

Suitable for open beams (RT1356)

Tested and assessed according to EN 13381-8 and EN 13381-9 (fire resistance up to 120 minutes)

CE-marked product with European Technical Assessment ETA-24/0831 Australia AS 4100

Fire resistanceClass B-s1, d0 (EN 13501-1)
Durability and serviceabilityZ2, Z1, Y (EAD 350402-00-1106)

ASTM E84: Class A. Other certificates and approvals are available on request.

Colour

White

Product Data

PropertyTest / StandardDescription
Volume SolidsISO 323373± 4 %
Flash PointISO 3679 Method 1101 °C
DensityTheoretical Value1.4 kg/L
RegionRegulationsTest / StandardVOC Value
USCARB(SCM)2020 / SCAQMD rule 1113Calculation22 g/L
Hong KongAir Pollution Control (VOC) RegulationCalculation22 g/L
EUEuropean Paint Directive 2004/42/CECalculation0 g/L

The data listed are based on factory batch production and may vary slightly with colour.

Solids content measured in accordance with ISO 3233 and the ASFP-BCF guidance method.

Film Thickness per Coat

Typical recommended specification range

Dry Film Thickness220–730 µm
Wet Film Thickness300–1000 µm

The final coat of a single-coat or multi-coat system may be applied to a wet film thickness of 1500 µm, depending on the steelwork configuration, geometry, primer used and surrounding environment. All steelwork shall be coated to the correct film thickness to achieve the required fire rating. Refer to the current thickness tables. For details, contact the local JOTUN office.

NoteThe single-coat film thickness applies to airless spray only.

Maximum permitted dry film thickness (BS and EN certificates)

Where measured thickness exceeds the limit, the measured thickness must be reduced by suitable means, based on the maximum thickness permitted by the profile and layout of the specific section.

I/H beam, 3 sides: 2878 µm. I/H beam, 4 sides: 2878 µm. I/H column, 4 sides: 3329 µm. CHS & RHS column, 4 sides: 1669 µm (BS standard only)

Surface Preparation

For further information, see the Application Guide.

Surface Preparation Summary

Surface Preparation

SubstrateMinimumRecommended
Coated surfaceA clean, dry and sound compatible primer.

Application

Application Methods

This product may be applied by the following methods

Spray:Apply by airless spray.
Brush:Recommended for touch-up and small-area application. Take care to achieve the specified dry film thickness.

Product mixing

One-component

Thinner / Cleaning Solvent

ThinnerFresh water

The product is ready to use. Thinning affects sag resistance and delays drying time.

CleanerFresh water

Airless Spray Guidance

Nozzle tip size (inch/1000):19-23
Nozzle pressure (minimum):200 bar/2900 psi

Drying and Curing Time

Substrate Temperature10 °C23 °C40 °C
Touch Dry4 h2 h1 h
Handle dry16 h6 h4 h
Minimum recoat interval16 h6 h4 h

For the maximum recoat interval, refer to the Application Guide (AG) for this product.

The minimum drying recoat interval is for self-recoating. See the additional guidance for the finish coat.

All drying times are measured at 1000 µm wet film, under controlled temperature and relative humidity below 80%.

The minimum application temperature for this product is 5 °C. For good application and drying, the steel and air temperatures should be above 10 °C.

Topcoat

The minimum recoat interval for applying a compatible topcoat over this product is 24 h.

The system should be dry to handle, and the coating thickness gauge must not leave indentations. Before applying the topcoat, the applicator must ensure the specified dry film thickness has been achieved.

Touch DryThe state at which light finger pressure leaves no mark or stickiness.
Handle dryThe minimum time after application before handling will not damage the film.

Minimum recoat interval after drying: the recommended minimum interval before applying the next coat.

Product Compatibility

Depending on the actual exposure conditions in service, this product may be used with various primers and topcoats. Some reference systems are listed below. For specific systems, contact JOTUN.

Previous coat:Alkyd, epoxy, epoxy zinc phosphate, zinc epoxy (with epoxy tie coat)
Subsequent coat:Approved topcoat list

Primers and topcoats used in the system must be compatible with the fire protection coating to ensure its fire performance. SteelMaster 900WF Intumescent Fire Protection Coating for Interior Steel Structures.

Contact your local JOTUN office for the approved primer and topcoat list.

Typical Packaging Sizes

VolumeContainer Size
(L)
SteelMaster 900WF Interior Intumescent Steel Fire Protection18.520

The packaging sizes above are typical reference sizes for factory batch production. Due to regional regulatory differences, packaging sizes and capacities may vary by region.

Storage

Store in accordance with national regulations. Keep containers in a dry, cool, well-ventilated place away from heat and sources of ignition. Keep containers tightly closed. Handle with care.

During storage or transport, the temperature shall be between 5 °C (41 °F) and 35 °C (95 °F). In addition, climate control is recommended. Avoid frost during transport and storage.

Shelf Life at 23 °C

SteelMaster 900WF 18 months Intumescent Fire Protection Coating for Interior Steel Structures

In some markets, the stated shelf life may be shortened to comply with local legal requirements. The above is the minimum shelf life; thereafter, testing is required to confirm quality remains acceptable.

Environmental documentation

This product can contribute to green building standard credits. Visit Jotun.com for more information or contact your local JOTUN representative.

EPDs are available at www.epd-norge.no

Precautions

For professional use only. Applicators and workers must be trained, experienced, capable and equipped to mix, stir and apply the coating correctly in accordance with JOTUN's technical documents. Applicators and workers must wear appropriate personal protective equipment when using this product. This guidance is provided based on current product knowledge. Any proposed modification to suit site conditions must be approved by the responsible JOTUN representative before use.

Health and Safety

Read the safety warnings on the container packaging. Use in well-ventilated conditions. Avoid inhaling spray mist and avoid skin contact. In case of accidental splashes on skin, wash immediately with a suitable cleaner, soap and water. In case of eye contact, rinse thoroughly with water and seek medical attention immediately.

Colour Variation

When used primarily as a primer or antifouling coating, products may show slight colour variation from batch to batch. Such products, and epoxy products used as topcoats, may chalk when exposed to sunlight.

Gloss and colour retention of topcoats depend on the colour type, the surrounding environment such as temperature and UV intensity, application quality and product type. Contact your local JOTUN office for further information.

Disclaimer

The information in this datasheet is based entirely on knowledge gained in our laboratory and in practice. JOTUN products are regarded as semi-finished products, and their use is generally beyond our control. JOTUN therefore guarantees only the quality of the product itself. To comply with local regulations, the product may be adjusted, and we reserve the right to modify the datasheet without further notice.

Users should consult JOTUN for specific guidance on the suitability of the product for their requirements and applications.

In case of any discrepancy between language versions, the English (UK) version shall prevail.

Information is subject to the manufacturer's latest version; the manufacturer's latest TDS prevails.
The technical parameters on this page are taken from the product's original manufacturer technical datasheet, the copyright of which belongs to the manufacturer. If a rights holder considers the presentation inappropriate, contact us for verification and handling.